TERMSTAR 1000
The radiant heating system TERMSTAR 1000 is a new, highly efficient dark gas infrared radiator with a power from 10 to 50 kW.
This heating is suitable for rooms from 50 m2 (car repair shops, MOT, tire repair shops, small halls, gyms)
- High energy efficiency
- Low temperature gradient (immediate readiness of the heating system and rapid achievement of operating temperature)
- Quick and easy assembly
- Reduced weight
- 1 and 2 stage operation
- Simplicity
Excellent radiation with an efficiency of 80-85%, achieved by the use of thermal insulation, further intensive recirculation of flue gas (flue gas is rotated several times in the pipe system and only then exits through the flue to the outside) and an optimal shape solution with a direct radiant effect.
Flue gas drainage and air suction
The flue gases from the TERMSTAR 1000 burner unit are always connected to the smoke flue pipe, through which the flue gases are drained out of the premises. The smoke flue can lead to the exterior through the ceiling or wall of the object. Smoke flues can be single-walled, double-walled with insulation for high chimneys, or coaxial to provide air suction from outside. Standard air suction intake for combustion is from the inner space of the object, or it is possible to use fresh air from outside.
TYPE OF GAS/LENGTH | TR15/4m | TR20/4m | TR20/6m | TR30/6m | TR40/8m | TR50/8m | |
---|---|---|---|---|---|---|---|
NATURAL GAS HG 20 | Burner nozzle | 3,8mm | 3,8mm | 3,8mm | 5,8mm | 5,8mm | 5,8mm |
Fan airflow flap | Ø28 | Ø32 | Ø32 | Ø45 | Ø55 | – | |
Fan flap | 32x36 | 32x36 | 32x36 | 40x45 | 58x58 | – | |
Burner flap | Ø50 | Ø50 | Ø50 | – | – | – | |
Pressure behind the regulator (mbar) 1-2 degrees | 8,0-4 | 14-4 | 14-4 | 6,7-3,6 | 12-8,5 | 16-7 | |
1-2 degree max/min (kW) | 15-10 | 20-10 | 20-10 | 30-20 | 40-30 | 50-30 | |
Launching (mbar) | 8 | 14 | 14 | 6,7 | 12 | 16 | |
PROPANE G31 | Burner nozzle | 2,2mm | 2,2mm | 2,2mm | 3,8mm | 3,8mm | 3,8mm |
Fan airflow flap | Ø28 | Ø32 | Ø32 | Ø50 | Ø60 | – | |
Burner flap | 32x36 | 32x36 | 32x36 | 40x45 | 58x58 | – | |
Throttle valves of the burner | Ø50 | Ø50 | Ø50 | – | – | – | |
Pressure behind the regulator (mbar) 1-2 degrees | 12-6,6 | 16-6,6 | 16-6,6 | 13-6,5 | 22-13 | – | |
Launching (mbar) | 12 | 16 | 16 | 13 | 22 | – |